Came out to call. Customer said system was tripping the breaker every so often, and it’s warm to the touch. I checked system over and found it to be working properly. Starting amps on compressor are high. Compressor is struggling a little when coming on. I suggested a hard start kit to help compressor on start up. Customer had me install it. I also s recommended having the breaker be changed to 40 amp instead of 30. It’s what is required for the system.