Joseph K.

Joseph K.


Job Checkin

I arrived for a non member heating to much call. I first inspected the system and found the thermostat to be in the off position and the system not running. I then inspected the entry way thermostat and the downstairs thermostat. I found the downstairs thermostat to be working properly. I found the entry way thermostats to be working but the display light would only come on when you pressed the body of the thermostats to the wall. It is not make a good internal electrical connection. I then cycled all zones on and check all electrical dampers. Zone 1 has one damper. Zone 2 has two dampers controlled by one thermostat. Zone 3 has one damper. I cycle all zones on one at a time to check that each thermostat is only operating one dampers on at a time. Zone dampers 1-3 are opening and closing with all demands given from 1-3 thermostats in heating and cooling modes. I check the bypass damper and for it to be operating properly with the air pressures per what zone was open/closed. We had a is