I arrived for a no cool recall. I found the secondary drain pan full of water and the p trap to be stoped up. I removed the p trap from this positive pressure draining line and reconnected the drains. I also found the the furnace and the evaporator coil to be sweating. Here is little attic vents to the attic. I recommend to add attic vents to help the system produce less water.