Rodney S.


Job Checkin

Non club tune up x 2. Main house. Furnace. Blower motor is ECM, no capacitor required, motor and wheel are clean, hot surface ignitor checked good, cleaned and checked flame sensor, pressure switch checked good, inducer motor run load amps are within mfg specs, all limits and safeties checked good, adjusted manifold pressure 4 in wc to 3.5 in wc to bring within mfg specs. Cycled system with stat and checked operation, no problems noted. Carbon monoxide was 0 ppm. System operating normally. Shop. Heat pump. Blower motor is ECM, no capacitor required. Checked heat strip operation, all sequencers operating normally, heat strip amps are good at 20A x 2. Heat pump. Replaced weak dual run capacitor, contactor is good. I initiated defrost, reversing valve shifted to cooling mode and condenser fan motor shut down. 1 minute later reversing valve shifted back to rest position and condenser fan motor resumed operation. All amps and pressures are good. Unit operating normally.