Joseph K.

Joseph K.


Job Checkin

I arrived to a no heat situation on a heat pump. During the inspection of the heat pump did notice that the low pressure switch was causing the unit to shut down and around the TXV in the heat pump there was frost. The heat pump does cycle on and off as well when the system does stabilize. Did find that the Capillary tube to the heat pump did break off most likely due to the unit rattling and that was causing the low pressure situation inside of the heat pump. The customer needs to speak with his wife before they will move forward with any repair or replacement which I did mention. I did also tell James that we have a finance company if they needed help with the repair. The customer will return a phone call to ask if and when they are ready. The unit has been shut down at the thermostat The customer has been informed that it is best to not try to run the unit. Please give us a call if you guys have any other questions.