9320 S. Pole Rd
Oklahoma City, OK 73160
(405) 794-8900

Our Top Cities


Job Locations
for shawnee, ok


Map of Shawnee OK
Jason B.

Jason B.


Job Checkin

04JUL2021 Jason B Arrived to new customer no cool, spoke with Brody about systems performance. Found contactor not making proper connection at AC. discussed options. With customer permission we agreed to do a tune up and replace the contactor. Inspected coil, blower cabinet, motor and all electrical components at the furnace. Inspected pressures, capacitors, fan, and compressor. Washed out condenser coils. Replaced damaged out of warranty contactor. Cycled system back on. Changed filters. 14x24 and 14x30. These are 3-month filters. Found returns undersized for system. This is a 3.5ton concord system with 1 14” and 1 10” return. Your system requires 1400 cfm for ideal performance you currently have 750 cfm. I recommend increasing both existing returns to 16” flex and cutting in a new return in the room that’s struggling to keep up.