Arrived to no cool service call and performed system evaluation. Found bad dual capacitor. Spoke to customer. Replace capacitor. Installed capacitor and compressor runs but condenser fan cuts out. Informed customer motor would need replacing. Customer is elderly and husband recently passed away. Customer having a little financing trouble. Spoke with customer. Will take half of payment today and rest in 30 days. Installed new motor. Started system. Amp draw in range. Refrigerant levels appear to be pretty close to in range. Superheat slightly high but most likely cause by hot temperatures in house. System is cooling at this time. 1yr motor warranty.