Kjofashions@yahoo.com Tech found the breaker for the outdoor system tripped. Tech reset compressor breaker during a cooling call and a loud buzzing was heard from the compressor, pressures did not move and lock rotor amps exceeded the limit specs. System is dirty, informed costumer about our ESA program. Tech diagnosed a locked compressor, tech checked compressor windings and for them to be on the Bad Mark, compressor has failed and locked. Mortex Split System is R22 refrigerant, 10+ years of age, Tech requested a field supervisor to provide homeowner with a solution, Scheduled to be here at noon. Heat pump is down as of now. Collected house call fee only by cash.