Derek J.

Derek J.


Job Checkin

Upon arrival tech began inspected second floor living room system and second and first floor zone system. Second floor for living and kitchen room had a failed dual run capacitor preventing the condenser from coming on as well a a dirt filter restricting air flow. Tech replaced capacitor and filter and system is back operational at this time. System for bedrooms on second floor and first floor also had a failed dual run capacitor and filters were dirty. Tech replaced capacitor and filters started system up and continued to give a 9 flash fault stating TXV stuck open or failed blower. Tech inspected blower to ensure there was sufficient airflow. Pressures were 127/247 with 1.6 SH and 2.8 SC indicating the TXV is stuck open. Estimate was emailed to homeowner for warranty TXV and wants to move forward with ordering.