Upon arrival tech began inspected second floor living room system and second and first floor zone system. Second floor for living and kitchen room had a failed dual run capacitor preventing the condenser from coming on as well a a dirt filter restricting air flow. Tech replaced capacitor and filter and system is back operational at this time. System for bedrooms on second floor and first floor also had a failed dual run capacitor and filters were dirty. Tech replaced capacitor and filters started system up and continued to give a 9 flash fault stating TXV stuck open or failed blower. Tech inspected blower to ensure there was sufficient airflow. Pressures were 127/247 with 1.6 SH and 2.8 SC indicating the TXV is stuck open. Estimate was emailed to homeowner for warranty TXV and wants to move forward with ordering.