12075 NW 40th Street #6
Coral Springs, FL 33065
877-574-1738

Job Locations
for davie, fl


Map of Davie FL
Phil G.

Phil G.


Job Checkin

We were dispatched for the following Had flooding down C, D, E, Y, and H aisles, little in B aisle last week. had roofing company here but they say no roof leaks. DM requesting maintenance on ac in the main building. Also, have a small leak on 2nd floor of 2nd building in front of unit A238. The following was found : Make : Trane Model : 4TEC3F42C1000AA Serial : 93554542V Delta -18 Solution : Replaced Run Capacitor 45+5 Installed Hard Start kit. Make : Carrier Model : 24ABC636A300 Serial : 0513E06859 Delta - 20 Solution : Replaced Run Cap 45+5 Make : Carrier Model : 24ABC636A00 Serial : 0513E06901 Delta - 20 Solution : Replace Run Cap 45+5 and Replaced Thermostat. Tech Notes : When I arrived I noticed multiple units not working as mentioned above. All 3 AC's had bad run cap's and one unit had a bad thermostat as well. Also put a hard start kit on one compressor. All 3 units now are working properly.