CUSTOMER PO#: 15032957 Today the Bard units (2) that serve the office were checked for cooling functions. These units are working and all tests performed were in proper range. The rooftop units (3) were checked. The West unit does have a compressor that is trying to run but then shuts down due to overheating. Time was spent diagnosing this issue and it was discovered that the contactor was arcing and there is a bad connection on one of the compressor leads. This was relayed to Dane and a service call to repair these items was approved verbally. The middle unit is functioning properly and the East unit is a heat only unit however the blower motor and wheel were checked and the filter was replaced. The units were all washed today and the drains were checked. A checkout sheet was filled out and emailed while on-site.