There was water in the inducer motor when I arrived. We got the inducer motor cleared out and then also checked the condensate pump. It started to work, but then the motor started to grind so the condensate pump will need to be replaced. After letting the system run, the furnace tripped out on the thermal limit. The ductwork is way too small for this size of furnace. The evaporator coil is also clogged up with dirt and debris. Between both of those the furnace was overheating. I showed and explained everything to customer. Customer would like to clean out the coiled themselves.