Arrived and discovered that the pilot light was no longer lit. There was a call for heat and 24v at the gas valve. The pilot was relit, gas pressure at inlet and manifold was checked, the furnace was cycled and observed four times. The furnace returned to operation once the pilot light was lit. The thermocouple was checked and I also confirmed that the pilot light was at the top 1/3 of the thermocouple and that the flame was not moving during operation. Thank you, Jon Tech notes: Inlet 7.88, manifold 3.38 Flames good, 22.5v at gas valve, pilot stays lit through multiple cycles.