1-17-22 Mon Men’s room steam room boiler not functioning correctly. Found the timer off by one hour due to daylight savings, made adjustments set a timer. During cycling of the boiler found that the temperature sensor had intermittent issues. Sensor had the correct resistance readings, however every few cycles it would not bring the boiler back on. There was a new sensor on site, shut down the system. Installed the new sensor correctly, per the instructions, system is working at this time. During cycling The steam valve is vibrating real bad I’m going to pick up a new rebuild kit