Completed cooling and heating tune up today. AC unit has restriction somewhere in the system as I had very high subcool and high superheat. System runs on R-22 refrigerant that is no longer manufactured. Customer has decided to go with replacing the unit. Furnace is operating properly at this time and I replaced the water panel with customer approval. Furnace is operating as expected. No gas leaks or CO detected today. Thank you for choosing LBA. Your technician today, Jake. View visual findings from this job here - https://visionshare.xoi.io/?id=XA-0D78-1044AAB9370D41748418DF77191DAF83