. Upon arrival went to indoor unit. The blower was running and amped at .93. The blower housing is clean. The coil is clean. Leak searched coil and found a leak. Went to outdoor unit. The refrigerant pressures were 5 psi. The compressor megohmmed in the green. The fan motor is in good shape. The capacitor checked out in range. The system has a 10 year parts warranty. Quoted everything up and went over it with the customer. The customer would like an estimate to replace the system as well to weigh his options. Called office and got him put on the schedule for the manager to come out today around 4-6:30. The system is currently down. Coil doesn’t need to be ordered unit customer fully approves quote for it after he gets a quote for a new system.