Unit 3 found bad cap causing the breaker to trip on compressor. Replaced cap and system started functioning found a very low superheat 1.5 degf customer declined looking into system any further Unit 4 found bad fan cap, unit is working okay. Found overcharged. Customer declined further diagnosis Mechanic was representing the company on site miguel