Club service A/C, changed customer supplied air filter, test ran system, 21 degrees delta t, compressor run load amps factory spec 14.1m actual 7.3, outdoor fan full load amps factory spec 1.5, actual 1.1, voltage enhancement system factory spec 45/5, actual 45.5/4.9, operation normal at this time.