Arrived to residence to perform hsp maintenance. Inspected furnace, ducts need cleaning, blower assembly ok, blower amps ok, capacitor within factory specifications, filter ok, drain clear, and had a 21 degree temperature difference. Outdoor coils clean, contactor not pitted or burned, fan motor running at high amps before replacing capacitor, capacitor rated 45/5 reading 38/1. Compressor and fan motor amps normal after replacing capacitor. System is operating normal at this time. Thanks for your business