Hsp004...hsp004... Arrived to complaint of home not cooling properly. Upon inspection found that system charge was off. Added 6oz of 410A as courtesy for customer signing up for priority Club. Pressures 115/315, Target SH 5.9F actual 6.3, SC rated at 15F actual 12.6F, 20F delta T. System is cooling properly. Customer signed up for HSP. Thank you for becoming a part of the My Plumber Heating and Cooling Family. You are much appreciated. Have a great day!