Heating repair. No heat call. Found water in the inducer motor due to a clogged condensation trap. Disassembled the inducer motor. Drained all the water. Resealed the inducer motor to the collector box. Retighten all collector box screws while the inducer motor is separated. Disassembled the condensation trap and all hoses. Washed/cleaned the trap and found tons of algae chunks that clogged the trap, causing water to backflow into the inducer motor. Reassembled everything and tested the heating system. Also found the flame sensor dirty. Cleaned flame sensor. The HVAC system is cleaned out and heating properly at this time. The customer joined the VIP maintenance program.