Checked in with customer Removed and replaced 20x3x1" filter in hallway Checked operation of AH. Verified fan operation and visual inspection Removed cover to condenser controls Checked voltage, 249.2 high, 27.8 low, good Checked contactor, good Checked all wiring and connections Found dual capacitor melted and common wire melted on bottom Replaced dual capacitor on separate WO Checked compressor, 1 bar on megohmmeter Checked and verified condenser fan motor operation Tested unit in cooling using old capacitor to verify operation Service complete