Contacted resident Went to roof Cleaned electric compartment Checked all wiring, good Checked heat exchanger, good Checked temperature rise rated 30-60 Supply air was 156 Return air was 74 Rise of 82, way to high Adjusted gas valve Supply air 130 Return air 80 Rise of 50,good Checked safety's, good Returned another day to deliver filters