Spring/April PM HVAC Preventative Maintenance Standard 180 Maintenance Deficiency for AC3 Package Unit Lennox LGA240HH2G 5602C06654: Found rtu with bad contactor , need a 3 pole 40 amp 24 v coil .also found defective 1 out door motor , recommend to replace along with a new blade and bracket and plastic shrout.motor is been hitting so blade is damage Deficiency for AC1 Package Unit Lennox LGA240HH2G 5602C06657: Found rtu 2 with 2 out door motors due to failing bearings . Recommend to change along with blade Suggested for AC2 Package Unit Lennox LGA240HH2G 5602C06652: Found rtu 2 with a broken out door motor palstic shrout . Need to replace . Also found bad crankcase heater for compressor 1 and bad pitted contactor 3 pole 40 amp 24 v Suggested for AC4 Package Unit Lennox LGA240HH2G 5602C06655: Found rtu with 2 bad pitted contactors, 3pole 24 v 40amp Suggested for AC5 Package Unit Lennox LGA300HH1G 5602C06579: Found 2 bad compressor contactors . Recommend to change out . Found al