Performed yearly Maintenance and safety checks on 2015 air conditioning system. System is running properly and within manufacture specifications at this time. Found concern involving compressor inrush amps high. Informed customer and presented options hn1 a-e. Customer chose option a. performed install of accessory. Inrush amps before install read 59 after install reduced to 34. No other concerns at this time.