Replaced water heater added expansion tank and added pan
Clean out pit and check if jammed with wipes no warranty found pump working properly and alarm system broken
Found unit calling for heat . Set to 69 and space was at 66 degrees . Heat pump was suppling 86 degree air with 66 coming back on the return . The electric heat was not coming on . Had to call tech support to get into programming of thermostat . They had me change to settings on there to allow the electric heat to come on . Tested system and the electric heat kick on in timers and first stage pulled 14.7 amps and supplied 94 degree air . Second stage pulled 31 amps and supplied 111 degree air. Called Alex and he told me to warranty to install . System is operating and has gone up two degrees since changing settings .