Found the system installed Incorrectly. The installers put duct work on a wall hung on the bottom then removed the drip plate and used it to block off front of unit. Removed the duct work put drip plate back where it belongs. The design of system because of the size of coil the drip plate has to be there. so all the home owner needs is to put a 20/18/1 filter.