I performed a complete tune up on the ac system and cleared the drain line with coil cleaner and water. I checked all electrical components and motors, refrigerant levels and temperature differentials. The condenser fan motor is overamping and the capacitor is starting to go weak. We will need to replace on our next visit ( it's a 45/5 reading 42.23/4.87). My refrigerant levels are good and I have a delta T of 21.5°. I loaded my pictures to service titan and left the system in proper working condition. I renewed the membership for the customer.