Performed routine maintenance on two complete mini split systems. Checked temps pressures drain lines amps volts coils filters etc. found system for Living room and kitchen 2 pounds low on refrigerant recommend leak search and repair Customer is just adding refrigerant and does not want to go forward with leak search at this time 10/20/21 Returned to customers home to perform leak search. I used my leak detector. Went inside and checked both heads for a leak in the coil and there was none. Went outside to the condenser and checked the whole coil and no leak. Pulled both side of the line set covers off and performed leak search on the line set in the back of house and no leak. Then I performed the leak search in the head in the front of house which is the living room and found a union leak on the liquid line side. I took 2 box wrenches and tighten the union. Put my leak detector back up to the line and no more leak. I fixed the leak and add about 2 pounds of Freon.