I found the condenser was tripped on High pressure switch, reset. The cause was that contractors working on the chimney covered the top of the condenser, set off on safety high head. The condenser fan blade is bent due to pieces of cement debris falling inside the unit. The condenser is shaking which will fail out the fan motor. The fan blade will be a warranty part, not labor. The contractor is pitted/ burnt due to safety head pressure switch setting off intermittently as it was covered. I found the pull out on disconnect is burnt up too. I put a quote together on repairs. They are interested in the pure airX to be installed in air handler. I will sanitize inside the air handler and install uv light in supply plenum..