3100 39th Ave North
St. Petersburg, FL 33714
727-822-7700

Job Locations
for st. petersburg, fl


Map of St. Petersburg FL
Nathan R.

Nathan R.


Job Checkin

Complete member tune up. Inspect filter location. I showed customers how to seat the filter properly. Clear and flush condensate pump. I cleared the PVC line going to the reservoir. I washed out the reservoir. I blew out the vinyl hosing going outside with nitrogen. At air handler, inspect electrical components. Test amps and volts. Delta t measures at 19 degrees. Ensure system is heating and cooling properly. A picture of the evaporator coil will be uploaded. The evaporator coil needs to be cleaned. The customers approved a pull and clean. At condenser checked pressures, temps, amps and volts. The high voltage contactor is extremely pitted and burnt. The customer approved replacing the contactor and work was complete. The low voltage wire at the condenser is deteriorating. We will need to splice the wire coming from the line-set cover to the unit to ensure no electrical shortages. The coil cleaning and wire repair will need to be completed at the same time. We will be able to return t