Arrived at customers for system inspection. On arrival customers showed me to air handler system. Air handler is equipped with pure air UV Bulb. Under evaporator coil was cleaning. Fan was clean. Vacuumed out drain line and heard good vacuum from upstairs. Unit had water in secondary drain Pan. Pointed out to customer. We were here in September so this is a courtesy drain pan vacuum. Unit is not equipped with a primary Float switch. Does have a drip line which I believe is taking in warm attic air and it is condensating and dripping out which is filling the secondary dream hand. Explained this to Customer and suggested they get a primary float switch. Customer agreed. Installed float switch and started unit. Unit started fine. Unit is producing proper Delta t. Next went outside to condenser. Open electric cabinet and tested components. Contact or sending proper voltage. Capacitor not within acceptable range. Point it out to customer and explain what capacitor did. Suggested she get a