Performed heating maintenance on a Goodman 96% efficient single stage natural gas furnace Collector box gasket is leaking water. We will send over a proposal to disassemble and replace the gasket kit Blower capacitor measured 15.2mfd (rated 15) Condensate lines are clear Corrected mounting of condensate trap inside the furnace Corrected humidifier drain by trimming some of the pipe shorter to take upward pressure off the housing Humidistat is incorrectly mounted downstream of the humidifier Recommend setting it higher than desired to ensure it humidifies Fixed a small leak on the exhaust pipe Flipped inducer outlet clamp 180⁰ per Goodman service bulletin Pulled flame sensor and cleaned Run tested furnace Humidifier is not leaking water at this time Set gas pressure to 3.0"wc Temperature rise with all 3 zone dampers open wax 35⁰ Closed all but one zone, temp rise peaked at 48⁰ Rated temp rise is 25-55⁰ Other than the leaking collector box gasket, system is working properly at thi

Performed heating maintenance on a Goodman 96% efficient single stage natural gas furnace
Collector box gasket is leaking water. 
We will send over a proposal to disassemble and replace the gasket kit
Blower capacitor measured 15.2mfd (rated 15)
Condensate lines are clear
Corrected mounting of condensate trap inside the furnace 
Corrected humidifier drain by trimming some of the pipe shorter to take upward pressure off the housing
Humidistat is incorrectly mounted downstream of the humidifier 
Recommend setting it higher than desired to ensure it humidifies
Fixed a small leak on the exhaust pipe
Flipped inducer outlet clamp 180⁰ per Goodman service bulletin
Pulled flame sensor and cleaned 
Run tested furnace 
Humidifier is not leaking water at this time 
Set gas pressure to 3.0"wc
Temperature rise with all 3 zone dampers open wax 35⁰
Closed all but one zone, temp rise peaked at 48⁰
Rated temp rise is 25-55⁰

Other than the leaking collector box gasket, system is working properly at thi Performed heating maintenance on a Goodman 96% efficient single stage natural gas furnace
Collector box gasket is leaking water. 
We will send over a proposal to disassemble and replace the gasket kit
Blower capacitor measured 15.2mfd (rated 15)
Condensate lines are clear
Corrected mounting of condensate trap inside the furnace 
Corrected humidifier drain by trimming some of the pipe shorter to take upward pressure off the housing
Humidistat is incorrectly mounted downstream of the humidifier 
Recommend setting it higher than desired to ensure it humidifies
Fixed a small leak on the exhaust pipe
Flipped inducer outlet clamp 180⁰ per Goodman service bulletin
Pulled flame sensor and cleaned 
Run tested furnace 
Humidifier is not leaking water at this time 
Set gas pressure to 3.0"wc
Temperature rise with all 3 zone dampers open wax 35⁰
Closed all but one zone, temp rise peaked at 48⁰
Rated temp rise is 25-55⁰

Other than the leaking collector box gasket, system is working properly at thi