Performed heating maintenance on a Carrier single stage 80% efficient natural gas furnace Filter is new *Recommend using 24x25x4 filters** Height of the 24x24x4 filter currently in place is a little short Blower is in OK condition Blower motor capacitor tested 9.6mfd (rated 10mfd) Pulled and cleaned flame sensor Ran combustion analyzer while performing run test of the furnace Combustion results are good, heat exchanger gets a passing grade Gas pressure set to 3.2"wc Temperature rise was 65⁰ (spec is 40-70) Blew out pressure switch port on the inducer housing No concerns found on today's visit Furnace is operating within factory specifications at this time

Performed heating maintenance on a Carrier single stage 80% efficient natural gas furnace
Filter is new
*Recommend using 24x25x4 filters**
Height of the 24x24x4 filter currently in place is a little short
Blower is in OK condition
Blower motor capacitor tested 9.6mfd (rated 10mfd)
Pulled and cleaned flame sensor
Ran combustion analyzer while performing run test of the furnace
Combustion results are good, heat exchanger gets a passing grade
Gas pressure set to 3.2"wc
Temperature rise was 65⁰ (spec is 40-70)
Blew out pressure switch port on the inducer housing
No concerns found on today's visit
Furnace is operating within factory specifications at this time Performed heating maintenance on a Carrier single stage 80% efficient natural gas furnace
Filter is new
*Recommend using 24x25x4 filters**
Height of the 24x24x4 filter currently in place is a little short
Blower is in OK condition
Blower motor capacitor tested 9.6mfd (rated 10mfd)
Pulled and cleaned flame sensor
Ran combustion analyzer while performing run test of the furnace
Combustion results are good, heat exchanger gets a passing grade
Gas pressure set to 3.2"wc
Temperature rise was 65⁰ (spec is 40-70)
Blew out pressure switch port on the inducer housing
No concerns found on today's visit
Furnace is operating within factory specifications at this time