Loose connection on low stage pressure switch causing system to lock out in pressure switch code. Tested induced draft at pressure switch amd confirmed proper vacuum to close switch. Confirmed no blockages in flue. Test ran system in both heating stages with no issues. Confirmed proper condensation drainage that rules out clogged drain trap. No other issues at this time but having a system maintenance to check and clean other things is recommended.