Prompt service and a great company to work with, would recommend to anyone
Replaced 10kw heat kit and 10mfd blower capacitor for system that services front studio. Replaced bad 45/5 mfd dual capacitor for back studio heat pump. Both systems are now operating properly.
Replaced control board and 24v double pole contactor for the #3 Trane gas package and system is now working properly. Pics uploaded Has a 1yr warranty on both parts Sending invoice to email for payment
Performed 3 system heat maintenance replaced 2 20x25x5 and 1 16x20x5 customer provided filters cleaned flame sensors and pressure tubes tested all electrical components and refrigerant charge all systems operating properly at this time
Member no fee- 2011 Gas Trane package system for room 3 not working because of a shorted control board and blower 24v double pole contactor. Will be calling supplier for part availability. Pics uploaded
Performed single system heat maintenance replaced both 20x25x5 filters cleaned flame sensor and pressure tubes tested all electrical components and connections inspected gas and exhaust supply all systems operating properly at this time
Replaced bad draft inducer pressure switch. Pressure switch was replaced earlier this year so it’s still covered under parts and labor warranty. System is now heating properly.
Performed 4 system heat maintenance tested safety’s cleaned flame sensors and pressure tubes tested all electrical components replaced 1 customer provided aprilaire 413 and 1 16x20x5 filter all other filters were still good tested refrigerant charge and auxiliary functions for basement system all systems operating properly at this time
No fee- Condensation pump for the main level system was accidentally kicked or moved and safety switch was triggered. I made corrections and system is now working properly. Not charging anything just in case it was me on 11-29-23. Pics uploaded
Zoned Main/Basment 2021 Goodman Heat pump/Air handler not working because of a shorted zone board and 1st level thermostat is shorted. Customer decided to approve the BEST option with board and thermostat replacement plus sign up for the comfort club membership. Parts are replaced and both upstairs and downstairs systems are serviced and working properly. 2-16x20x1, pics uploaded Has a 1yr warranty on parts
I performed a maintenance on two gas furnace one in the attic and one in the garage. I checked all the low voltage and checked the blower motor amperage and compaster I also cleaned the flame sensor off the filters are fine and still look new. The systems are running and operating likely should be at this time.
The thermostat was locked and wouldn’t change over to heat showed her out to unlock the thermostat. The system is running and operating like it should be at this time.
Completed two system heating maintenance. I replaced 2-16x20x1 filters at air handlers. I checked amp draw on the blower motor and heat strips. I checked all electrical components temperature rise across the coils. Both systems are currently operating at manufacturers specifications.
Replaced the shorted thermostat and contactor was replaced 8/28/23. Room 4 Trane package system is now working properly. Pics uploaded (Control board was not needed). Sending invoice to email
I installed the contactor and the control bored is bad now
The bed room 4 contactor system is bad and will not pull in