13211 Veterans Memorial Hwy.
Douglasville, GA 30134
770-203-0274

Our Top Cities


Local Reviews
for folkston, ga


Job Locations
for folkston, ga

Tyler L.

Tyler L. Job Checkin

Generator faulted for Throttle Stuck on 5/29/23 and Throttle Position on 5/15/23. No evidence of a coolant leak or oil leak. Manually moved throttle and watched feedback circuit work properly. Started generator and allowed it to run for roughly 30 minutes monitoring for leaks. No issues found. Will need to monitor for continued Throttle issues.


Rodney N.

Rodney N. Job Checkin

Certified Generac start up. Generator is working properly. Paid $350 with check #516.


Rodney N.

Rodney N. Job Checkin

Annual service. Replaced battery during service. Generator is working properly.


Rodney N.

Rodney N. Job Checkin

#1 service. Generator is working properly.


Rodney N.

Rodney N. Job Checkin

#1 service. Generator is working properly. Paid PMA check #8022. $450


Rodney N.

Rodney N. Job Checkin

#2 service. Replaced controller no charge per Cheryl. Generator is working properly.


Rodney N.

Rodney N. Job Checkin

Bad controller and battery. Replaced and tested. Generator is now working properly.


Tyler L.

Tyler L. Job Checkin

Generator shutdown for low coolant. The heater core block off cap(rubber cap) was deteriorated and ruptured. See attached pictures. Replaced cap and topped off coolant level. Power was still out so generator was placed into auto. Generator started and immediately powered building. Monitored generator for further issues. No evident issues present.


Rodney N.

Rodney N. Job Checkin

#2 service. Generator is working properly.u


Rodney N.

Rodney N. Job Checkin

#1 service. Generator is working properly. Customer will cut back the shrubs around generator. Fire barrier must be installed after customer has made it possible to do so.


Rodney N.

Rodney N. Job Checkin

Could not get generator to duplicate the rpm loss. Did a firmware update and performed a #2 service. Generator is working properly.


Rodney N.

Rodney N. Job Checkin

#1 service. Generator was leaking antifreeze from a faulty hose clamp. Replaced both clamps. Drained antifreeze and refilled. Had to add one gallon. Generator is now working properly.


Rodney N.

Rodney N. Job Checkin

#1 service. Generator is working properly. Customer paid PMA over the phone.


Rodney N.

Rodney N. Job Checkin

#2 service. generator is working properly. Sealed window.


Rodney N.

Rodney N. Job Checkin

#2 service. Generator is working properly.