After our builder drop the ball on our generator Anderson came in with their team and knock it out very quickly. Anderson is professional and friendly and I highly recommend their work... thanks to Gunner, Alex and Caleb my system works properly...
W101493 JB50356088 Sub panel 162-828 is actually the outside main disconnect next to the meter, the other 3 indoor sub panels were photographed and noted
#2 service. Generator is working properly.
#2 service. Generator is working properly.
JB5014699 Replaced block heater during ATS major
JB49841556 Added fuel during service
JB48960650 Added 40 gallons of diesel during minor
Generator needs new mag pick up. due to RPM sense loss. GENERATOR UNDER (WARRANTY)
Customer didn’t want surge protector due to it not covering her whole house
PO-14879
Spot Cooler 1- 5-Ton AC Includes Duck work and Pig tails Delivery after hours
Upon arrival to service gen, found gen in shutdown fault. After inspection found that the battery terminals were severely corroded and damaged. Also found the starter to be burnt up from trying to start with damaged battery cables. Recommend replacing the battery cables, battery, and starter. *Unit still needs service.
Arrived for a callout and found unit leaking coolant. Found small hole in water pump hose. Recommend repplacing all coolant hoses, thermostat and radiator cap.
power Cycled power meter JB45785754 CM-3169604
Labor to travel and confirm Bad TVSS module and quote installing cables to monitor other TVSS units