Customer is having power issues throughout home. I opened the panel and tested voltage coming into the home and found that there is only 174.4 volts between the 2 hot legs and roughly 86 volts individually on each leg to ground. This is a power company issue. I informed customer to contact BG&E to have issue resolved. I turned off the larger equipment (240 volt) in home at the panel so that they don’t get damaged. Once issue is resolved by power company they can be turned back on by customer.