Customer showed me where the previous company installed the double oven. The double oven had a whip coming out of the unit that went into a 11 b box and they had wire nuts on it with the existing electrical line which was aluminum 6-3 seu cable The wrong connector from the whip of the oven was installed which resulted in the whip coming loose from the 11b junction box. Also the wire nuts are not rated to be used properly in this situation with a oven that draws a lot of energy. This is why the wires burnt up which is a major safety hazard I installed a junction box and had the whip from the double oven go to that. Then i ran a 6-3 romex from that to the junction box that was feeding the electrical circuit. I installed screw down Permanent bugs to make all my connections due to the heavy load of the circuit and the line feeding the circuit was aluminum Customer has a 30 day warranty on work preformed #review