Nicholas T.

Nicholas T.


Job Checkin

Outlets on pier were completely submerged on the last large storm. This caused the GFCI outlet closet to the house to short out. I removed the 2 original outlets and installed new weatherproof boxes at the top of the pylons with the lift motors and installed new weatherproof outlets with in-use covers. I ran a new 12/2 UF wire from the 1st outlet to the 2nd one. I removed the standard breaker and installed a dual function CH breaker to protect circuit. Once completed i turned everything on and it all worked properly.