Ran a new dedicated 30 amp circuit from the main panel out to the back porch outside the basement door and installed a new 30 amp inlet power box for a portable generator. We installed the box next to A/c line set. We installed an interlocking kit in the main panel so that the generator breaker and the main breaker cannot be on at the same time. We checked all the wiring on the back porch and only needed to repair the wiring at a junction box above the back walk out door. There was no signs of water damage in the lights or the wiring above the lights.