Customer had a power outage in 4 kitchen area outlets. Outlets were protected by a gfci in the beginning of he circuit. Gfci would not reset after tripping, removed device and found there was 120v on the line side indicating that the device had failed. Replaced the gfci and restored power to rest of circuit. Customer also said they felt like they were being shocked by kitchen switches. Replaced both switches for overhead light to make sure no voltage was leaking. There was also an issue in the bathroom with the light failing to turn on previously. After looking at switches noticed that the three way was failing and arcing on the inside. Replaced all switches in the bathroom. If any other devices have an issue they will also need to be replaced. Verified proper operation of all completed work with customer.