Customer stated no heat and weird noise. Upon inspection found dirty evap and condenser. Also notice no filter. System has weak airflow. Heat strip pulling 40 amps. Duct work is run all over the place with a lot of it being pinched and a lot of Ys which can cause weak airflow. Found a bad outdoor capacitor. Put one on to further test system and found system not circulating pressures properly. Based off pressures customer has a clogged piston or stuck piston. Would need to recover all refrigerant, replace filter dryer, clean piston, and recharge system. Created quotes to of all repairs done. Presented to customer. Highly recommended customer replace system due to cost of repair and older 410 refrigerant. Customer decided to have install supervisor out to receive a new system quote.