Arrived today, Scott explained to us that the GFCI that is controlling power to his septic pump and septic alarm we’re not working properly anymore. After testing the GFCI, we found that both receptacles had good power coming to them, but both receptacles were defective. We replaced both GFIC receptacles, and we also replaced. The weatherproof bubble covers on top of them because they were old and worn out. There was also moisture inside of the covers like they had been wet a little bit. Once both receptacles and bubble covers were installed both of the new receptacles worked properly. We also mounted the new septic alarm box on the backside of the strut directly behind the receptacles. While we were here, Scott, also talk to me about three separate other projects he would like estimate estimates on, which will be attached to the invoice email. It was very nice meeting both of you today! If you all have any questions about the estimates or need anything else, please feel free to give