Following morning found ceiling grid and tile (8) then down. Have to bring in Electrician and ceiling repair to fix the issue. This type of damage or grease on the roof is becoming the norm.
Portable Extinguishers, Emergency / Exit Lights, and Kitchen Suppression Inspection 5: FP Annual 12: FP Annual Ansul R102 3 gal: FP Semi Annual Inoperable Deficiency: Ansul system is red tagged and needs repairs done now!!!!!!! Parts needed are,3 gal ansulex,101-30 cartridge, hose, bursting disc, 4x scissors, 1x 3 gal stainless tank hydro tested, and regulator tested, also needs 1x G2-301 emergency light, 3x 4.5 ah battery’s. Labor est is about 3x hours. Deficiency for 12: Exit light by back door and emergency lights by back door and cash register failed inspection and Need replaced Need 2 G2-301 emergency lights 1 G1-101 exit light