Alarm Systems Inspection FP Annual Deficiency: Batteries in FACP failed load test and are due for replacement
Fire Alarm Deficiency Found: Power Supply/NAC Panel Replacement Needed During a recent service call for your fire alarm system, the technician discovered that the power supply NAC panel located on the 3rd floor was inoperable due to an AC/charging board failure. Immediate replacement of this power supply NAC panel is required to restore functionality and ensure that notification systems are operational again. Nelbud proposes to replace the power supply NAC panel located on the 3rd floor to resolve this deficiency. The proposal below is all-inclusive and includes all parts and labor. You can accept this proposal electronically or contact me directly. Alarm Systems Repair 3rd floor NAC panel is defective due to AC/Charging board failure and needs to be replaced. Need to replace FCPS-24S8 power supply & (2) 12v7ah batteries. This exact power supply panel is obsolete so we will need to install a compatible replacement 4 hour labor. Inoperable Deficiency: 3rd floor NAC panel needs to
Alarm Systems Service Call service call needed for alarm Inoperable Deficiency: 3rd floor NAC panel needs to be replaced.