Fire Alarm Deficiency Found: Heat Detector expired NFPA 72 Table 14.4.2.2, Item 14.d.3].After 15 years from initial installation all devices shall be replaced or 2 detectors per 100 shall be laboratory tested. The 2 detectors shall be replaced with new devices If a failure occurs on any of the detectors removed, additional detectors shall be removed and tested to determine either a general problem involving faulty detectors or a localized problem involving 1 or 2 defective detectors. If detectors are tested instead of replaced, tests shall be repeated at intervals of 5 years Alarm Systems Repair 6- out of date/ recalled spot type heat detectors (Only to be in use for 15 years) (These installed are from 1989) 2- 194 degree conventional heats 4- 135 degree conventional heats - repair 2 painted smoke detectors 1- in gaming section 1- above bar Will need 2- 2WB smoke detectors - repair Deficiency: 1 painted smoke detector in office Deficiency: During inspection found 2 painted smok