Portable Extinguishers, Emergency / Exit Lights, and Kitchen Suppression Inspection By back door, kitchen 2: FP Annual FP Annual e lights Buckeye BFR-20 BFR-20 By back door: FP Semi Annual Inoperable Deficiency for Buckeye BFR-20 BFR-20 By back door: There is no gas shut off on system. There is no electrical shut off. Gauge has been hit and is loose and will rotate. Can not verify if tank has lost pressure or not. Will need 2” electric or mechanical gas valve and for micro switch to be wired to shut electric. Will need new gauge & recharge on BFR-20 tank. CAN NOT VERIFY IF TANK IS CHARGED AND WILL FUNCTION CORRECTLY!!!! Inoperable Deficiency: 2 exit lights are not emergency lights. Need replaced with 2-LED4B combo units.
Emergency / Exit Lights and Portable Extinguishers Inspection
Portable Extinguishers and Kitchen Suppression Inspection
Kitchen Suppression and Portable Extinguishers Inspection Ansul R-102 3gal By back door in kitchen System 3: FP Semi Annual Ansul 3g Ansul R-102 3gal System2- Hall between kitchen & dinning: FP Semi Annual Ansul 3g Ansul R-102 6gal System1- Above pull stations: FP Semi Annual Ansul 6g 2 in kitchen, 1 in hall between kitchen and dining 3: FP Annual