51 Koweba Lane
Indianapolis, IN 46201
(855) 932-6437

Our Top Cities


Local Reviews
for connersville, in

Rated 5.0 out of 5 stars based on 5 customer reviews

Great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great

His tech notes are always clear and accurate. We almost never after to follow up to ask questions about his inspections. Recommends when necessary

  • Overall Experience
  • Quality
  • Price
  • Convenience

Quiet, Respectful,

He kept to himself. He done what he needed to get done and was very quiet in the process. He was no bother at all and the only thing negative I can say is he moved our fire extinguisher from one place to another with out telling us so we had to look. It wasn't far :)

  • Overall Experience
  • Quality
  • Price
  • Convenience

Professional!

Always professional.great to work with!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service!

Always prompt. Keeps us in compliance.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for connersville, in

Kelii K.

Kelii K. Job Checkin

Portable Extinguishers, Emergency / Exit Lights, and Kitchen Suppression Inspection By back door, kitchen 2: FP Annual FP Annual e lights Buckeye BFR-20 BFR-20 By back door: FP Semi Annual Inoperable Deficiency for Buckeye BFR-20 BFR-20 By back door: There is no gas shut off on system. There is no electrical shut off. Gauge has been hit and is loose and will rotate. Can not verify if tank has lost pressure or not. Will need 2” electric or mechanical gas valve and for micro switch to be wired to shut electric. Will need new gauge & recharge on BFR-20 tank. CAN NOT VERIFY IF TANK IS CHARGED AND WILL FUNCTION CORRECTLY!!!! Inoperable Deficiency: 2 exit lights are not emergency lights. Need replaced with 2-LED4B combo units.


Jaymes B.

Jaymes B. Job Checkin

Emergency / Exit Lights and Portable Extinguishers Inspection


Jaymes B.

Jaymes B. Job Checkin

Kitchen Suppression Inspection


Jaymes B.

Jaymes B. Job Checkin

Portable Extinguishers and Kitchen Suppression Inspection


Kelii K.

Kelii K. Job Checkin

Kitchen Suppression and Portable Extinguishers Inspection Ansul R-102 3gal By back door in kitchen System 3: FP Semi Annual Ansul 3g Ansul R-102 3gal System2- Hall between kitchen & dinning: FP Semi Annual Ansul 3g Ansul R-102 6gal System1- Above pull stations: FP Semi Annual Ansul 6g 2 in kitchen, 1 in hall between kitchen and dining 3: FP Annual


Jaymes B.

Jaymes B. Job Checkin

Portable Extinguishers and Emergency / Exit Lights Inspection


Jaymes B.

Jaymes B. Job Checkin

Kitchen Suppression Inspection