Kitchen Suppression Inspection Buckeye BFR BFR-10: FP Semi Annual Buckeye BFR 10
Kitchen Suppression Inspection FP Semi Annual FP Semi Annual Ansul Ansul 3 gallon -3 gallon-3 gallon: FP Semi Annual Deficiency for Ansul Ansul 3 gallon -3 gallon-3 gallon: Potato fryer and chicken fryer. Both need updated from old pneumatic switches to micro switches to properly test electrical shut down. Also noticed no automatic gas shut off for both appliances. Will need to installed electrical or mechanical gas valve to correct issue .